제로에너지 주택용 요소기술 조합에 따른 에너지절감에 관한 연구

癔襸耔* ; 笙忨竩**
Energy Saving by Combination of Element Technologies of Zero-Energy House
Shin, Hyun-Cheol* ; Jang, Gun-Eik**
*Energy Environment Technology Center, Korea Conformity Laboratories, South Korea theshc@kcl.re.kr
**Corresponding author, Department of Advanced Materials Engineering, Chungbuk National University, ChungBuk, Korea gejang@chungbuk,ac,kr


ⓒ Copyright Korea Institute of Ecological Architecture and Environment

Abstract

Purpose

In 2008, As the green growth policy was presented, Green Building is made any effort to propagation. In this paper, the respective technologies that are able to considerably reduce the energy demands for heating, cooling, hot-water, lighting and ventilation among the variety of technologies were selected.

Method

Design factors such as ① External insulation, ② Triple glazing window, ③ LED lighting, ④ External venetian blind, ⑤ Geothermal and ⑥ Heat recovery ventilator were derived. In addition, energy saving effects in terms of energy demand, energy consumption and energy cost were investigated using EnergyPlus, building energy analysis tool.

Result

The results were as follows. (1) It can be seen that high insulated triple glazing window, heat recovery ventilator and external insulation technology is excellent for energy demand. (2) Unlike energy demand, saving effect of energy consumption and energy cost was shown in order of Geothermal > Triple Window > Heat recovery Ventilation> Insulation> LED Lighting > EVB Blind.

Keywords:

Zero Energy, Passive House, Green Home, Element Technology

키워드:

제로에너지, 패시브주택, 그린홈, 요소기술

1. 서론

1.1. 연구의 배경 및 목적

전 세계적으로 기후변화에 대응해 에너지 소비를 줄이기 위한 다양한 노력이 시도되고 있지만 그 효과는 아직 미흡하며, 온실가스 감축 및 저탄소 녹색성장 구현을 위하여 건축물 분야의 역할이 매우 중요하다. 국내의 경우 건축물 부문의 에너지소비량은 국가 전체 에너지소비량의 약 25%를 차지하고 있으며, 그중 가정에서 소비되는 에너지가 53%를 차지하고 있다.

국내의 경우 2008년 녹색성장정책이 제시·추진되면서 법과 제도를 정비하는 등 친환경 건축물 보급에 많은 노력을 기울이고 있다. 또한, 국내 건물 에너지 절감을 위한 정책은 2017년까지 주거용 건축물의 경우 60 %, 일반건축물의 경우 30 %의 에너지 감축을 목표로 하고 있으며, 2025년 건축물 제로에너지 의무화를 목표로 정책이 추진되고 있다.1)

이에 본 연구에서는 제로에너지 주택을 구현하기 위한 핵심 요소기술 7가지를 선정하고, 에너지 절감요소, 신재생에너지 냉난방 및 발전기술의 조합에 따른 에너지 요구량, 소비량 및 에너지 비용을 정량적으로 분석함으로써, 건축물의 초기 계획단계에서 활용을 목적으로 한다.

1.2. 연구의 방법 및 범위

본 연구는 단독 주택의 에너지 절감을 위한 다양한 기술들 가운데 2000년 중반부터 지어진 대표적인 ‘그린홈(Green Home)’을 대상으로 표 1 과 같이 건축적, 설비적, 신재생에너지 요소기술로 분류하였다. 이를 바탕으로 공통적으로 적용되고 냉난방, 급탕, 조명 및 환기 에너지요구량을 크게 절감할 수 있는 민감도가 큰 적용 기술들을 분석하여 설계 변수들을 도출하였다.

도출된 설계 변수들로 적용 가능한 조합들을 선정하고, 기존의 건물 에너지 절약 설계기준에 입각한 주택과 각 기술들이 복합적으로 적용될 Case의 향별, 요소기술 적용별, 태양광 발전으로 구분하여 에너지 요구량, 소비량 및 에너지 비용을 정량적으로 분석함으로써, 에너지 절감 효과를 정량적으로 산정하였다.

따라서 본 연구는 분석 모델 선정에서부터 공통 요소기술 도출 및 평가 전반에 걸쳐 기준 모델에 대한 절감 효과에 초점을 맞추어 연구를 진행하였다.

본 연구는 시뮬레이션을 통한 분석 연구로 미국 DOE-2와 BLAST의 장점을 통합하여 개발한 EnergyPlus 엔진을 기반으로 하는 DesignBuilder v.3.0을 이용하여 수행되었다. DesignBuilder는 EnergyPlus의 대표적인 3rd Party 인터페이스 프로그램이다.

Analysis of Domestic and Abroad Zero Energy Housing Element Technologies


2. 선행연구 고찰

2.1. 선행연구 고찰

이와 관련하여 많은 연구들이 수행되고 있다. 송승영 (2012년)등은 공동주택을 대상으로 요소기술을 도출하고, 에너지효율 분석 및 비용효율을 분석하였다. 이명주 (2011년)등은 에너지 시뮬레이션을 통해 국내 단독주택, 건축물에너지절약설계기준, 패시브하우스 기준을 상호 비교하면서 건축물 에너지 절감 요소기술 별 에너지 절감량 및 절감률을 도출하였으며, 김빛나 (2010년)등은 패시브 주택의 절감 목표를 설정하고, 이를 충족하기 위한 최적의 부하저감 요소기술 구성방법에 대한 대안을 도출하였다. 윤종호 (2007년)등은 고층 아파트를 제로에너지화 하기 위해 적용할 수 있는 핵심기술들을 분류하고 각 기술들에 대한 에너지 절감효과를 정량적으로 분석하였다. 기존연구의 분석결과, 주로 에너지소비량을 중심으로 분석이 이루어 졌으며, 패시브주택 설계에 요소기술에 따른 민감도 및 건물자체의 재실자 쾌적능력, 설비 용량을 산정할 수 있는 근거 자료로 활용될 수 있는 에너지요구량 분석은 미비한 실정이다.

이에 본 연구에서는 제로에너지 주택을 구현하기 위한 핵심 에너지요구량 요소기술 7가지를 선정하고, 에너지 절감요소, 신재생에너지 냉난방 및 발전기술의 조합에 따른 에너지 요구량, 소비량 및 에너지 비용을 정량적으로 분석하였다.


3. 시뮬레이션 구성

3.1. 시뮬레이션 모델 선정

시뮬레이션 모델은 ‘강원도 보급형 저탄소 주택모형 개발’ 이라는 보급형 주택 설계 및 설계도서 개발 연구를 통하여 우리나라 기후에 적합하고 에너지절감에 유리하도록 계획·검증된 주택이다. 바닥면적 101.88 ㎡, 층고 2.4 m로 남북측에 상대적으로 넓은 창을 갖는 특징이 있으며, 대상 시뮬레이션 모델링과 주택의 평면도는 그림 1과 같다.

Fig 1.

Modeling of Target House

3.2. 기본안 및 요소기술 입력조건

시뮬레이션 분석에 앞서 기본가정을 살펴보면 다음과 같다.

① 대상 주택의 기본안을 구성하기 위하여 사용된 벽체 및 창호구성은 「‘건축물의 에너지절약설계기준’의 [별표 2] 단열재 두께와 [별표 3] 창 및 문의 단열성능」을 참고하였다. ② 요소기술중 외단열은 외벽에 250 ㎜ 적용되었으며, 지붕과 바닥은 기본안의 단열재 두께에서 250 ㎜로 증가시켜 적용하였다. ③ 창호의 경우 기본안은 Low-e 복층유리로 침기횟수는 0.7 회/h로 적용시켰고, 요소기술의 경우 고기밀 3중 Low-e유리로 중간유리를 제외한 최외측과 내측 유리의 내부면에 코팅된 것으로 침기횟수는 0.1 회/h로 향상시켜 적용시켰다. ④ LED 조명은 기본안(형광등) 대비 2.26W/㎡ (약 33%)의 에너지가 절약된다고 가정하였으며, 외부 전동블라인드(External Venetian Blind : 이하 EVB라 칭함)는 Slate 각도를 90°(수평 방향)로 고정하고 여름철 4개월만 사용되고 나머지 월은 사용되지 않도록 스케줄을 조절하였다. ⑤ 냉난방 및 급탕의 경우 일반 보일러 및 에어컨 대비 난방 COP 4.5(급탕열공급비율 8%), 냉방 COP 3.5의 Water to Air 타입의 지열히트펌프를 개선안으로 적용시켜 분석하였다. ⑥ 기본안의 강제환기장치는 2013년 개정된 ‘건축물의 설비기준 등에 관한 규칙’의 0.5 ACH보다 충분한 환기량 확보를 통한 공기질 개선을 위하여 개정 이전 기준인 0.7 ACH로 적용하였으며, 폐열회수 환기 장치는 효율 80%로 적용시켰다. 시뮬레이션을 위해 적용된 요소기술은 다음 표 2와 같다.

Input Condition of Simulation Element Technologies

시뮬레이션을 위해 공통으로 적용된 입력조건은 표 3과 같으며, 기상데이터는 IWEC에서 제공하는 인천지역 기상데이터 자료를 사용하였다.

Input Condition of Common Application

3.3. 시뮬레이션 케이스 구성

Simulation Case & Application Element Tech.

시뮬레이션은 표 4와 같으며, 먼저 향별 분석은 기본안(남향)을 포함하여 4가지 케이스로 구성하였고, 적용 요소 기술 조합에 따른 2차에너지 요구량 비교가 가능하며, 지열시스템은 냉난방설비 시스템의 변화로 2차에너지 소비량으로 판단하여야한다. 또한 태양광 발전은 각 용량과 설치경사각도를 조합하여 발전량을 산출하였다.


4. 시뮬레이션 분석 결과

4.1. 에너지 환산계수

건물에너지 분석의 범위는 내부기기를 제외한 난방, 냉방, 조명, 환기, 급탕에너지의 2차 에너지요구량 및 소비량으로 한정하였다. 2차 에너지소비량은 2차 에너지요구량과 표 5, 6의 각 에너지에 따른 환산 계수(설비의 성능과 운전효율을 적용)로 나누어 산출하였으며, 1차 에너지소비량은 2차 에너지소비량에 표 7의 1차 에너지환산계수를 곱하여 산출하였다. 또한 가스 및 전기 요금은 2차 에너지소비량에 표 8의 평균단가를 곱하여 산출하였다.

Conversion Factor of Secondary Energy Consumption _(excluded Geothermal)

Conversion Factor of Secondary Energy Consumption _(included Geothermal)

Conversion Factor of Primary Energy

Unit Price of Gas & Electricity

4.2. 기본안의 향별 에너지 분석

먼저 기본안에 대한 방위에 따른 건물에너지의 영향도를 분석하였으며, 그 결과는 표 9와 같다.

표 9에서 알 수 있듯이 종합적인 향별 에너지요구량은 일사에 따른 건물의 평면과 창호의 분포 특성에 의하여 남향>북향>서향>동향의 순서로 에너지 성능이 우수한 것으로 나타났다. 난방 에너지요구량은 남향이 12,567 kWh로 가장 낮은 분포를 나타내고 있으며, 서향이 12,976 kWh로 다음으로 낮게 나타나고 있다. 그러나 서향은 냉방에너지 요구량이 가장 높게 나타나는 특징이 있으며, 북향은 난방은 높으나 냉방은 낮은 특징이 있으며, 이는 분석 대상 모델의 공간배치 특성에 따른 것으로 판단된다.

Annual Secondary Energy Demand_Orientation

표9의 에너지요구량을 2차 에너지 소비량으로 변환해 나타내면 표 10과 같다. 조명과 환기는 전기를 직접 사용하므로 환산계수 및 효율이 적용되지 않지만, 난방 및 급탕의 경우에는 가스를 사용한 보일러 및 에어컨을 이용하고, 냉방의 경우에는 전기를 사용하지만 COP와 운전효율의 영향을 받게 된다. 따라서 2차 에너지 요구량의 분석 결과와는 다소 차이가 나타나게 되며, 남향>서향>북향>동향의 순서로 2차 에너지 소비량이 우수한 것으로 나타난다. 전체적으로 건물이 서향으로 향했을 경우 일사에 따른 영향으로 냉방부하가 가장 높게 나타나지만, 상대적으로 난방부하는 적게 나타나는 것을 알 수 있다. 또한 주어진 대상 모델에서는 건물이 동향으로 향할 때 가장 높은 에너지 소비량을 나타내는 것을 알 수 있다. 따라서 건물은 가능한 한 남향을 향하도록 배치시키는 것이 에너지적으로 가장 우수함을 다시 한 번 확인할 수 있었다.

Annual Secondary Energy Consumption_Orientation

Annual Energy Cost & Saving Rate_Orientation

표 11은 표 8의 요금을 적용하여 에너지 비용을 산정한 것이다. 에너지원별 가격 차이의 발생으로 2차 에너지 소비량의 비율과 다소 차이는 발생하지만, 전체적인 분포 패턴은 동일하게 나타나고 있음을 알 수 있다.

4.3. 요소기술 조합에 따른 에너지 요구량

각 요소 기술 조합에 따른 2차 에너지 요구량, 소비량 및 에너지 비용을 살펴보면 다음과 같다.

Annual Secondary Energy Demand

Fig 2.

Annual Secondary Energy Demand

표 12와 그림 2는 요소기술 조합별 2차 에너지요구량을 나타낸 것이다. 2차 에너지 요구량 분석을 통하여 설비 용량을 산정할 수 있는 근거 자료로 활용될 수 있고, 각 요소기술들이 건물에너지에 미치는 영향을 파악할 수 있다. 그리고 에너지 요구량이 높다는 것은 설비 시스템이 없을 경우 재실자의 쾌적감이 낮아지게 됨을 의미한다. 단일 요소기술을 적용하였을 경우 2차 에너지 요구량 측면에서 고기밀 3중창호를 적용한 경우 가장 큰 절감율인 21.8%를 나타내고 있다. 이는 단열성능과 기밀성능이 동시에 향상되어 난방 및 냉방부하를 동시에 감소시키기 때문이다. 다음으로 폐열회수 환기 장치와 외단열을 이용한 슈퍼 단열 기술이 효과가 높은 것으로 분석되었다. LED 조명기구의 경우에는 조명부하를 약 30% 절감시키는 동시에 냉방 부하도 절감시키지만, 내부발열이 줄어 난방부하는 오히려 상승시키는 작용을 하게 되는 것을 알 수 있다. EVB 전동 블라인드의 경우에는 냉방부하 절감효과는 크나 난방부하가 다소 증가 전체적으로는 약 1.7%의 절감효과만을 나타내는 것을 알 수 있다. 지열 시스템의 경우, 별도의 부하저감기술이 적용되지 않았기 때문에 냉난방 에너지 요구량이 기준안과 동일하게 나타났다.

따라서, 패시브 주택을 구현함에 있어 가장 먼저 고려해야 할 대상은 고성능, 고기밀성 창호>고효율 폐열회수 환기장치>외단열 순서인 것으로 분석되었다.

4.4. 요소기술 조합에 따른 에너지 소비량

다음으로 에너지 요구량을 충족시키기 위하여 표 2에서 제시한 냉난방 설비 시스템을 적용한 경우의 에너지 소비량을 분석한 결과는 표 13 및 그림 3과 같다.

Fig 3.

Annual Secondary Energy Consumption

Annual Secondary Energy Consumption

에너지 소비량 분석의 경우, 설비성능, 운전효율 및 사용 에너지원 등의 이유로 요소기술에 따라 요구량과는 상이한 결과를 나타내고 있음을 알 수 있다. 단일 요소기술의 적용시 표 12의 에너지 요구량과는 달리 Case-5인 지열 시스템의 절감율이 약 78%로 가장 큰 절감효과를 나타내고 있다. 초기 투자비용에 대한 부담만 없다면 가장 합리적인 시스템인 것으로 분석되었다.

또한 외단열과 3중창이 적용된 Case에서 에너지소비량이 낮게 나타나는 경향을 보였다. 이러한 에너지 소비량은 에너지 비용과 직접적으로 연결이 되는 것이다.

4.5. 요소기술 조합에 따른 에너지 비용

각 요소 기술 조합에 따른 에너지 비용을 살펴보면 다음과 같다. 다음으로 표 8의 평균단가를 이용하여 표 13을 에너지 비용 측면에서 정리한 것이 표 14 및 그림 4와 같다.

Annual Energy Consumption Cost

Fig 4.

Annual Energy Consumption Cost

에너지 소비비용 측면에서는 2차 에너지 소비량과 유사한 분포를 나타내고 있으며, 운전비용 절감 효과 역시 지열 요소기술을 포함하여 적용하였을 경우 에너지 비용 절감효과가 큰 것으로 나타났으며, 지열 > 3중창 > 폐열회수 환기장치 > 외단열 > LED 조명기구 > 외부 전동차양장치의 순으로 나타났다.

지열을 사용하였을 경우 단위면적당 1차 에너지 소요량이 83.5 kWh/㎡으로 가장 낮은 것으로 분석 되었으며, 2차 에너지 소비량과 유사한 분포를 나타내고 있다.

요소기술 중 지열을 포함하는 Case에서 에너지 소비량이 낮은 것으로 나타났다. 이는 다른 요소기술에 비하여 지열의 에너지 절감폭이 커 지열을 포함하고 있는 Case에서 2차 에너지 소비량이 낮게 나타나는 것으로 판단된다.

4.6. 태양광 발전

태양광 발전은 발전 용량은 1 kWp 급, 2 kWp 급, 3 kWp 급으로 하였고, 각각에 대한 경사각도는 0°, 15°, 30°, 45°로 12가지 분석 케이스로 가정하여 발전량을 산출하였으며, 표 15와 같다.

Photovoltaic Installation Angle & Power Output according to Generation Capacity

태양광 발전량은 각 요소 기술별 연간 2차 에너지 소비량에서 차감 될 수 있다. 분석결과 발전용량이 증가할수록 절감비용이 큰 것으로 나타났으며, 여름철 태양고도의 영향으로 설치각도 30°에서 발전용량 및 절감비용이 가장 크며, 각도 증가하면서 다시 줄어드는 것으로 나타났다. 또한 설치각도의 변화에 따라서 최대 약 11.73% 증가하는 것으로 분석되었다.


5. 결론

본 연구는 국내외 그린홈 사례 분석을 통하여 일반 주택의 에너지 절감을 위한 다양한 기술들 가운데 냉·난방, 급탕, 조명 및 환기 에너지 요구량을 크게 줄일 수 있는 대표적인 기술로 ①외단열, ②3중창, ③LED 조명, ④EVB 블라인드, ⑤폐열회수 환기 장치, ⑥지열 시스템을 선정하고, 그린홈의 요소기술별 에너지 소비량 및 소비비용을 정량적으로 분석하였다.

그 결과를 요약하면 다음과 같다.

(1) 주어진 대상 건물의 경우, 방위에 따른 건물에너지의 영향도를 분석한 결과 2차 에너지 요구량은 남향>서향>동향>북향의 순서로 나타났으며, 2차 에너지 소비량은 COP 및 운전효율의 영향에 따라서 남향>서향>북향>동향의 순서로 우수한 것으로 2차 에너지 요구량과는 다소 차이가 있는 것으로 나타났다.

(2) 요소기술 조합에 따른 분석 결과, 에너지 요구량 측면에서는 고기밀 3중창호를 적용한 경우 단열성능과 기밀성능의 향상으로 가장 큰 절감율인 21.8%를 나타냈다. 다음으로 폐열회수 환기장치와 외단열 기술이 효과가 높은 것으로 분석되었다. 에너지 소비량을 분석한 결과, 에너지 요구량과는 달리 지열 시스템이 가장 큰 절감효과를 나타내고 있다. 2가지 요소기술을 적용하였을 경우 외단열+3중창을 적용하였을 경우와 3중창+폐열회수 환기시스템을 적용하였을 경우 기준안 대비 절감율이 각각 31.3%, 36.9%로 가장 높게 나타났다.

(3) 에너지 소비비용의 경우, 에너지 소비량과 유사한 분포를 나타냈으며, 운전비용 절감 효과는 에너지 요구량과는 달리 지열>3중창>폐열회수 환기장치>외단열>LED 조명기구>전동 외부차양장치의 순으로 나타났다.

이상의 연구를 통해 주택에 적용될 수 있는 요소기술의 조합에 따른 에너지 소비량 및 에너지비용 분석을 실시하였으며, 정량적인 데이터를 통해 건축물 계획시 활용가능한 자료이다. 요구량 분석을 통해 고성능 창호, 외단열 등과 같은 건축요소들 또한 건축물 에너지 절감량의 큰 효과를 보이는 것을 알 수 있으며, 제로에너지 하우스 보급에 앞서 패시브 주택의 보급을 위해 건축적 요소의 연구와 개발이 지속적으로 이루어져야 할 것이다. 또한 현재 국내에서는 2025년까지 건축물 제로에너지 의무화를 목표로 정책이 추진되고, 그린홈 및 패시브주택 등 다양한 시범주택들이 건축되고 있지만, 일반적으로 건설되고 있는 주택의 경우 공동주택에 비해 에너지를 다소비하는 것이 현실이다. 따라서 국가적으로 정량적인 에너지 평가와 경제성 분석을 통한 제로에너지 주택보급이 절실히 필요하다.

이에 추후 연구에서는 요소기술의 조합에 따른 에너지비용 분석을 통해 설계단계에서 이용할 수 있도록 각 요소기술의 조합에 따른 LCC 분석을 통하여 최적 조합 방법에 관한 후속 연구가 수행될 예정이다.

Notes

1) 제1차 녹색건축물 기본계획, 제2차 녹색성장 5개년 계획

Reference

  • 김빛나, 윤종호, 신우철, 백남춘, (2010), 패시브주택 에너지 절감목표 수준별 요소기술 통합구성에 관한 연구, 한국태양에너지학회, 30(2), p240-426.
    Kim, Bich-na, Yoon, Jong-Ho, Shin, U-Cheul, Beak, Nam-Choon, Optimal Configuration of Energy Conservation Measures for Meeting the Target Energy Saving Ratio of Passive House, Journal of the Korean Solar Energy Society, Korea, 30(2), (2010).
  • 송승영, 이수진, 허갑수, 진현호, (2012), 제로에너지 공동주택을 위한 주요 설계변수별 비용효율 분석, 대한건축학회논문집, 8(28), p207-216.
    Song, Seung-Yeong, Lee, Soo-Jin, Hur, Kab-Soo, Jin, Hyun-Ho, Cost Efficiency Analysis of Design Elements for a Zero Energy Apartment Building, Journal of Architectural Institute of Korea, Korea, 8(28), (2012).
  • 윤종호, (2007), 공동주택의 에너지 자립을 위한 핵심요소기술의 에너지 성능평가, 한국태양에너지학회 논문집, 27(3), p161-167.
    Yoon, Jong-Ho, Kim, Byoung-Soo, Energy Performance Evaluation of Zero Energy Technologies for Zero Energy Multi-House, Journal of the Korean Solar Energy Society, Korea, 27(3), (2017).
  • 이명주, 김원석, 이우주, 이원택, (2012), 건축물에너지절약요소기술 적용에 따른 단독주택 에너지 요구량 절감률 변화에 관한 연구, 대한건축학회논문집, 28(5), p275-282.
    Lee, Myoung-Ju, Kim, Won-Seok, Lee, Woo-Joo, Lee, Won-Taek, A Study about Reduction Rates of Building Energy Demand for a Detached House according to Building Energy Efficient Methods, Journal of Architectural Institute of Korea, Korea, 28(5), (2012).
  • 이종식, 강혜진, 박진철, 이언구, (2009), 공동주택 건축기술 요소의 CO2 배출성능평가에 관한 연구, 대학건축학회논문집, 25(9), p275-284.
    Lee, Jong-Sik, Kang, Hea-Jin, Park, Jin-Chul, Rhee, Eon-Ku, A Study on the CO2 Emission Performance Assessment of the Sustainable Building Technologies for Multi-Family Residential Buildings, Journal of Architectural Institute of Korea, Korea, 25(9), (2009).

Fig 1.

Fig 1.
Modeling of Target House

Fig 2.

Fig 2.
Annual Secondary Energy Demand

Fig 3.

Fig 3.
Annual Secondary Energy Consumption

Fig 4.

Fig 4.
Annual Energy Consumption Cost

Table 1.

Analysis of Domestic and Abroad Zero Energy Housing Element Technologies

Domestic Abroad
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
① Green Tomorrow, ② Eco-3L House, ③ GreenHome Zero House, ④ ZeSH Ⅱ ⑤ GreenhomePlus
⑥ Passive House (Germany) ⑦ Zero-Energy House (United Kingdom) ⑧ Zero House (USA) ⑨ Carbon Zero House (Japan)
Passive Design High Heat Insulation ● ● ● ● ● ● ●
Triple Window ● ● ● ● ● ● ● ● ●
Double Skin Facade ●
Natural Ventilation ●
Roof Planting ● ●
Active Design Heat Recovery Ventilation ● ● ● ● ● ● ● ● ●
Under Floor Air Conditioning ●
Radiant Heating & Cooling ● ●
LED ● ● ●
New-Renewable Energy Photovoltaic ● ● ● ● ● ● ● ●
Geothermal ● ● ● ● ● ●
Wind Power ● ● ●
Water Heating ● ● ● ● ● ●
Fuel Cell ● ●
Rainwater ● ●

Table 2.

Input Condition of Simulation Element Technologies

Element Tech. Object Basis Application
Outside Insulation (250 ㎜) Outer wall 0.324 W/㎡・K 0.150 W/㎡・K
Roof 0.271 W/㎡・K 0.150 W/㎡・K
Floor 0.263 W/㎡・K 0.150 W/㎡・K
Triple Window Window 2.40 W/㎡・K
Infiltration : 0.7 ACH
1.00 W/㎡・K
Infiltration : 0.1 ACH
LED Lighting Lighting 6.80 W/㎡ 4.54 W/㎡
EVB Blind Shading - May~Aug : ON
(Slate angle-90°)
other : OFF
Geothermal System Heating Cooling Boiler : COP 0.85
(Efficiency : 70%)
Geothermal Heat-pump
Heating COP : 4.5
Cooling COP : 3.5
(Efficiency : 80%)
Air-con : COP 3.5
(Efficiency : 60%)
Heat Recovery Ventilator Ventilation Number of ventilation : 0.7 ACH Efficiency : 80%
Photovoltaic Renewable - by Capacity
(1, 2, 3 kWp)
Orientation Environment South (Base) East, West, South, North

Table 3.

Input Condition of Common Application

Subsection Input Condition
Set-point Heating : 22 ℃ / Cooling : 25 ℃
People Bedroom Living room / Toilet
0.022 people/㎡ 0.0188 people/㎡
Apparatus Bedroom Living room Toilet
3.58 W/㎡ 3.90 W/㎡ 1.67 W/㎡
Hot-water 0.53 ℓ/㎡・day
Target illumination 100~200 lux
Weather Data KOR_INCH'ON_IWEC

Table 4.

Simulation Case & Application Element Tech.

CASE Outside Insulation (250㎜) Triple Window LED Lighting EVB Electric Blind Geothermal System Heat Recovery Ventilator
South × × × × × ×
East × × × × × ×
North × × × × × ×
West × × × × × ×
1 kinds C-01 ○ × × × × ×
C-02 × ○ × × × ×
C-03 × × ○ × × ×
C-04 × × × ○ × ×
C-05 × × × × ○ ×
C-06 × × × × × ○
2 kinds C-07 ○ ○ × × × ×
C-08 ○ × ○ × × ×
C-09 ○ × × ○ × ×
C-10 ○ × × × ○ ×
C-11 ○ × × × × ○
C-12 × ○ ○ × × ×
C-13 × ○ × ○ × ×
C-14 × ○ × × ○ ×
C-15 × ○ × × × ○
C-16 × × ○ ○ × ×
C-17 × × ○ × ○ ×
C-18 × × ○ × × ○
C-19 × × × ○ ○ ×
C-20 × × × ○ × ○
C-21 × × × × ○ ○
3 kinds C-22 ○ ○ ○ × × ×
C-23 ○ ○ × ○ × ×
C-24 ○ ○ × × ○ ×
C-25 ○ ○ × × × ○
C-26 ○ × ○ ○ × ×
C-27 ○ × ○ × ○ ×
C-28 ○ × ○ × × ○
C-29 ○ × × ○ ○ ×
C-30 ○ × × ○ × ○
C-31 ○ × × × ○ ○
C-32 × ○ ○ ○ × ×
C-33 × ○ ○ × ○ ×
C-34 × ○ ○ × × ○
C-35 × ○ × ○ ○ ×
C-36 × ○ × ○ × ○
C-37 × ○ × × ○ ○
C-38 × × ○ ○ ○ ×
C-39 × × ○ ○ × ○
C-40 × × ○ × ○ ○
C-41 × × × ○ ○ ○
4 kinds C-42 ○ ○ ○ ○ × ×
C-43 ○ ○ ○ × ○ ×
C-44 ○ ○ ○ × × ○
C-45 ○ ○ × ○ ○ ×
C-46 ○ ○ × ○ × ○
C-47 ○ ○ × × ○ ○
C-48 ○ × ○ ○ ○ ×
C-49 ○ × ○ ○ × ○
C-50 ○ × ○ × ○ ○
C-51 ○ × × ○ ○ ○
C-52 × ○ ○ ○ ○ ×
C-53 × ○ ○ ○ × ○
C-54 × ○ ○ × ○ ○
C-55 × ○ × ○ ○ ○
C-56 × × ○ ○ ○ ○
5 kinds C-57 ○ ○ ○ ○ ○ ×
C-58 ○ ○ ○ ○ × ○
C-59 ○ ○ ○ × ○ ○
C-60 ○ ○ × ○ ○ ○
C-61 ○ × ○ ○ ○ ○
C-62 × ○ ○ ○ ○ ○
6 kinds C-63 ○ ○ ○ ○ ○ ○
Photovoltaic 1, 2, 3 kWp

Table 5.

Conversion Factor of Secondary Energy Consumption _(excluded Geothermal)

Energy Heating Cooling Lighting Ventilation Hot-water
(Heating/Hot-water - Efficiency 70% of COP 0.85
Cooling - Efficiency 60% of COP 3.5)
Conversion Factor 0.6 2.1 1 1 0.6
Energy Source Gas Electricity Electricity Electricity Gas

Table 6.

Conversion Factor of Secondary Energy Consumption _(included Geothermal)

Energy Heating Cooling Lighting Ventilation Hot-water
Geothermal Heating/Hot-water - Efficiency 80% of COP 4.5,
Geothermal Cooling - Efficiency 80% of COP 3.5)
Conversion Factor 3.6 2.8 1 1 3.6
Energy Source Geothermal Geothermal Electricity Electricity Geothermal

Table 7.

Conversion Factor of Primary Energy

Division Fuel Electricity District Heating District Cooling
Primary Energy Conversion Factor 1.1 2.75 0.614 0.937

Table 8.

Unit Price of Gas & Electricity

Energy Source Unit Price (won/kWh) Calculate Standard
Gas 72.61 City Gas Calorific - 10,400 kcal/㎥
Seoul City Gas Co. - 874.15 won/㎥ (2012)
Electricity 103.38 Sales Cost of Residential Electricity (2010)

Table 9.

Annual Secondary Energy Demand_Orientation

Orientation Heating Cooling Lighting Ventil. Hotwater Total
[kWh]
South 12,567 1,762 899 56 1,001 16,285
East 13,530 1,958 899 56 1,001 17,444
North 13,324 1,733 899 56 1,001 17,014
West 12,976 2,110 899 56 1,001 17,041

Table 10.

Annual Secondary Energy Consumption_Orientation

Orientation Heating Cooling Lighting Ventil. Hot-water Total
[kWh]
South 21,120 839 899 56 1,682 24,597
East 22,740 933 899 56 1,682 26,309
North 22,394 825 899 56 1,682 25,856
West 21,808 1,005 899 56 1,682 25,450

Table 11.

Annual Energy Cost & Saving Rate_Orientation

Orientation Gas Electricity Total
Cost (1,000won) Saving rate (%) Cost (1,000won) Saving rate (%) Cost (1,000won) Saving rate (%)
South 1,656 0.0% 185 0.0% 1,841 0.0%
East 1,773 -7.1% 195 -5.2% 1,968 -6.9%
North 1,748 -5.6% 184 0.8% 1,932 -4.9%
West 1,706 -3.1% 202 -9.2% 1,908 -3.6%

Table 12.

Annual Secondary Energy Demand

Case Secondary Energy Demand [Unit : kWh]
Heating Cooling Lighting Ventil. Hot-water Total
Base 12,567 1,762 899 56 1,001 16,285
1 kinds 1 10,990 1,811 899 56 1,001 14,757
2 9,147 1,625 899 56 1,001 12,728
3 12,720 1,684 600 56 1,001 16,061
4 12,667 1,385 899 56 1,001 16,008
5 12,567 1,762 899 56 1,001 16,285
6 10,121 1,791 899 16 1,001 13,827
2 kinds 7 7,534 1,692 899 56 1,001 11,182
8 11,143 1,726 600 56 1,001 14,526
9 11,101 1,362 899 56 1,001 14,418
10 10,990 1,811 899 56 1,001 14,757
11 8,529 1,876 899 16 1,001 12,321
12 9,298 1,543 600 56 1,001 12,498
13 9,224 1,309 899 56 1,001 12,489
14 9,147 1,625 899 56 1,001 12,728
15 6,728 1,625 899 16 1,001 10,268
16 12,823 1,312 600 56 1,001 15,792
17 12,720 1,684 600 56 1,001 16,061
18 10,268 1,711 600 16 1,001 13,596
19 12,667 1,385 899 56 1,001 16,008
20 10,212 1,394 899 16 1,001 13,522
21 10,121 1,791 899 16 1,001 13,827
3 kinds 22 7,682 1,604 600 56 1,001 10,943
23 7,613 1,307 899 56 1,001 10,876
24 7,534 1,692 899 56 1,001 11,182
25 5,035 1,731 899 16 1,001 8,682
26 11,258 1,284 600 56 1,001 14,199
27 11,143 1,726 600 56 1,001 14,526
28 8,675 1,791 600 16 1,001 12,083
29 11,101 1,362 899 56 1,001 14,418
30 8,626 1,399 899 16 1,001 11,941
31 8,529 1,876 899 16 1,001 12,321
32 9,378 1,229 600 56 1,001 12,264
33 9,298 1,543 600 56 1,001 12,498
34 6,868 1,545 600 16 1,001 10,030
35 9,224 1,309 899 56 1,001 12,489
36 6,789 1,297 899 16 1,001 10,002
37 6,728 1,625 899 16 1,001 10,268
38 12,823 1,312 600 56 1,001 15,792
39 10,364 1,317 600 16 1,001 13,298
40 10,268 1,711 600 16 1,001 13,596
41 10,212 1,394 899 16 1,001 13,522
4 kinds 42 7,766 1,225 600 56 1,001 10,648
43 7,682 1,604 600 56 1,001 10,943
44 5,169 1,642 600 16 1,001 8,428
45 7,613 1,307 899 56 1,001 10,876
46 5,079 1,334 899 16 1,001 8,329
47 5,035 1,731 899 16 1,001 8,682
48 11,258 1,284 600 56 1,001 14,199
49 8,777 1,317 600 16 1,001 11,711
50 8,675 1,791 600 16 1,001 12,083
51 8,626 1,399 899 16 1,001 11,941
52 9,378 1,229 600 56 1,001 12,264
53 6,934 1,220 600 16 1,001 9,771
54 6,868 1,545 600 16 1,001 10,030
55 6,789 1,297 899 16 1,001 10,002
56 10,364 1,317 600 16 1,001 13,298
5 kinds 57 7,766 1,225 600 56 1,001 10,648
58 5,221 1,248 600 16 1,001 8,086
59 5,169 1,642 600 16 1,001 8,428
60 5,079 1,334 899 16 1,001 8,329
61 8,777 1,317 600 16 1,001 11,711
62 6,934 1,220 600 16 1,001 9,771
6 kinds 63 5,221 1,248 600 16 1,001 8,086

Table 13.

Annual Secondary Energy Consumption

Case Secondary Energy consumption [Unit : kWh]
Heating Cooling Lighting Ventil. Hot-water Total
Base 21,120 839 899 56 1,682 24,597
1 kinds 1 18,471 863 899 56 1,682 21,970
2 15,374 774 899 56 1,682 18,785
3 21,378 802 600 56 1,682 24,518
4 21,289 659 899 56 1,682 24,586
5 3,491 629 899 56 278 5,353
6 17,009 853 899 16 1,682 20,459
2 kinds 7 12,662 806 899 56 1,682 16,104
8 18,728 822 600 56 1,682 21,888
9 18,657 648 899 56 1,682 21,942
10 3,053 647 899 56 278 4,933
11 14,334 893 899 16 1,682 17,825
12 15,626 735 600 56 1,682 18,699
13 15,503 623 899 56 1,682 18,763
14 2,541 580 899 56 278 4,354
15 11,308 774 899 16 1,682 14,678
16 21,551 625 600 56 1,682 24,514
17 3,533 601 600 56 278 5,069
18 17,258 815 600 16 1,682 20,371
19 3,519 494 899 56 278 5,246
20 17,164 664 899 16 1,682 20,424
21 2,811 640 899 16 278 4,644
3 kinds 22 12,910 764 600 56 1,682 16,013
23 12,795 623 899 56 1,682 16,055
24 2,093 604 899 56 278 3,930
25 8,463 824 899 16 1,682 11,884
26 18,920 611 600 56 1,682 21,870
27 3,095 616 600 56 278 4,646
28 14,579 853 600 16 1,682 17,730
29 3,084 486 899 56 278 4,803
30 14,497 666 899 16 1,682 17,760
31 2,369 670 899 16 278 4,232
32 15,761 585 600 56 1,682 18,685
33 2,583 551 600 56 278 4,068
34 11,543 736 600 16 1,682 14,577
35 2,562 468 899 56 278 4,263
36 11,410 618 899 16 1,682 14,624
37 1,869 580 899 16 278 3,642
38 3,562 469 600 56 278 4,965
39 17,418 627 600 16 1,682 20,344
40 2,852 611 600 16 278 4,358
41 2,837 498 899 16 278 4,527
4 kinds 42 13,053 583 600 56 1,682 15,974
43 2,134 573 600 56 278 3,641
44 8,687 782 600 16 1,682 11,767
45 2,115 467 899 56 278 3,815
46 8,536 635 899 16 1,682 11,768
47 1,399 618 899 16 278 3,210
48 3,127 459 600 56 278 4,520
49 14,751 627 600 16 1,682 17,677
50 2,410 640 600 16 278 3,944
51 2,396 500 899 16 278 4,089
52 2,605 439 600 56 278 3,978
53 11,654 581 600 16 1,682 14,533
54 1,908 552 600 16 278 3,354
55 1,886 463 899 16 278 3,542
56 2,879 470 600 16 278 4,243
5 kinds 57 2,157 437 600 56 278 3,529
58 8,775 594 600 16 1,682 11,667
59 1,436 587 600 16 278 2,917
60 1,411 476 899 16 278 3,080
61 2,438 470 600 16 278 3,803
62 1,926 436 600 16 278 3,256
6 kinds 63 1,450 446 600 16 278 2,790

Table 14.

Annual Energy Consumption Cost

Case Energy Cost [Unit : 1,000won]
Gas Electricity Total
Cost Saving Rate Cost Saving Rate Cost Saving Rate
Base 1,656 0% 185 0% 1,841 0%
1 kinds 1 1,463 11.6% 188 -1.3% 1,651 10.3%
2 1,238 25.2% 179 3.6% 1,417 23.0%
3 1,674 -1.1% 151 18.7% 1,825 0.9%
4 1,668 -0.7% 167 10.0% 1,835 0.3%
5 274 83.5% 164 11.7% 437 76.2%
6 1,357 18.0% 183 1.5% 1,540 16.4%
2 kinds 7 1,041 37.1% 182 1.9% 1,224 33.5%
8 1,482 10.5% 153 17.6% 1,635 11.2%
9 1,477 10.8% 166 10.6% 1,643 10.8%
10 242 85.4% 166 10.7% 407 77.9%
11 1,163 29.8% 187 -0.8% 1,350 26.7%
12 1,257 24.1% 144 22.5% 1,401 23.9%
13 1,248 24.6% 163 12.0% 1,411 23.4%
14 205 87.6% 159 14.4% 363 80.3%
15 943 43.0% 175 5.9% 1,118 39.3%
16 1,687 -1.9% 132 28.6% 1,819 1.2%
17 277 83.3% 130 29.9% 407 77.9%
18 1,375 16.9% 148 20.3% 1,523 17.3%
19 276 83.3% 150 19.2% 426 76.9%
20 1,368 17.4% 163 12.0% 1,532 16.8%
21 224 86.5% 161 13.4% 385 79.1%
3 kinds 22 1,060 36.0% 147 20.8% 1,206 34.5%
23 1,051 36.5% 163 12.1% 1,214 34.0%
24 172 89.6% 161 13.1% 333 81.9%
25 737 55.5% 180 3.1% 916 50.2%
26 1,496 9.6% 131 29.3% 1,627 11.6%
27 245 85.2% 132 29.1% 377 79.6%
28 1,181 28.7% 152 18.1% 1,333 27.6%
29 244 85.3% 149 19.7% 393 78.6%
30 1,175 29.0% 163 11.9% 1,338 27.3%
31 192 88.4% 164 11.7% 356 80.7%
32 1,267 23.5% 128 30.8% 1,395 24.2%
33 208 87.5% 125 32.7% 333 81.9%
34 960 42.0% 140 24.7% 1,100 40.3%
35 206 87.5% 147 20.7% 353 80.8%
36 951 42.6% 158 14.6% 1,109 39.8%
37 156 90.6% 155 16.7% 310 83.1%
38 279 83.2% 116 37.3% 395 78.5%
39 1,387 16.2% 129 30.7% 1,515 17.7%
40 227 86.3% 127 31.6% 354 80.8%
41 226 86.3% 146 21.3% 372 79.8%
4 kinds 42 1,070 35.4% 128 30.9% 1,198 34.9%
43 175 89.4% 127 31.5% 302 83.6%
44 753 54.5% 145 22.1% 897 51.3%
45 174 89.5% 147 20.7% 321 82.6%
46 742 55.2% 160 13.6% 902 51.0%
47 122 92.6% 158 14.6% 280 84.8%
48 247 85.1% 115 37.9% 363 80.3%
49 1,193 27.9% 129 30.7% 1,322 28.2%
50 195 88.2% 130 30.0% 325 82.3%
51 194 88.3% 146 21.2% 340 81.5%
52 209 87.4% 113 39.0% 323 82.5%
53 968 41.5% 124 33.3% 1,092 40.7%
54 159 90.4% 121 34.9% 279 84.8%
55 157 90.5% 142 23.2% 300 83.7%
56 229 86.2% 112 39.4% 342 81.4%
5 kinds 57 177 89.3% 113 39.0% 290 84.3%
58 759 54.1% 125 32.5% 884 52.0%
59 124 92.5% 124 33.0% 249 86.5%
60 123 92.6% 144 22.5% 266 85.5%
61 197 88.1% 112 39.4% 310 83.2%
62 160 90.3% 109 41.4% 269 85.4%
6 kinds 63 125 92.4% 110 40.8% 235 87.2%

Table 15.

Photovoltaic Installation Angle & Power Output according to Generation Capacity

Generation Capacity 1 kWp 2 kWp 3 kWp
Installation Angle
0° Generation [kWh] 1,095 2,190 3,504
Saving cost [won] 113,211 226,402 362,264
15° Generation [kWh] 1,191 2,382 3,811
Saving cost [won] 123,126 246,230 393,981
30° Generation [kWh] 1,223 2,447 3,915
Saving cost [won] 126,465 252,940 404,722
45° Generation [kWh] 1,194 2,388 3,820
Saving cost [won] 123,394 246,830 394,891