Home > Current Issue > Vol. 19, No. 1


[ Research Articles ]
The International Journal of The Korea Institute of Ecological Architecture and Environment - Vol. 18, No. 6, pp.61-68
Abbreviation: J. Korea Inst. Ecol. Archit. And Environ.
ISSN: 2288-968X (Print) 2288-9698 (Online)
Print publication date 31 Dec 2018
Received 23 Oct 2018 Revised 29 Nov 2018 Accepted 04 Dec 2018
DOI: https://doi.org/10.12813/kieae.2018.18.6.061

건물의 에너지 성능 향상을 위한 주택정비기술의 중요도 분석 : 소단위 정비사업을 위한 노후 단독주택을 중심으로
안상민* ; 김성우** ; 최소라** ; 백지나** ; 김성완***

The Importance Analysis of Energy Conservation Measures for the Building Energy Performance Improvement in existing single-family houses: Focused on Low-income Detached House for Small Unit Development Project
An, Sang Min* ; Kim, Sung Woo** ; Choi, Sora** ; Baek, Jina** ; Kim, Sung Wan***
*Main author, Korea Research Institute of Eco-Environmental Architecture, South Korea (walterlook@naver.com)
**Coauthor, Korea Research Institute of Eco-Environmental Architecture, South Korea (smith78@naver.com)(s425730@naver.com)(qorwlsk1029@hanmail.net)
***Corresponding author, Korea Research Institute of Eco-Environmental Architecture, South Korea (swankim4016@naver.com)

@ 2018 KIEAE Journal
Funding Information ▼

Abstract
Purpose:

This study is to evaluate the building energy performance of the detached house standard model depending on the application of the different kinds of energy conservation measures such as the double glazing window, internal insulation reinforcement, the high efficiency boiler, and LED lightings, etc.

Method:

The building energy consumption and savings of each energy conservation measure is analyzed making use of the dynamic building energy simulation. When it comes to the importance analysis of energy conservation measures, the payback period and life cycle cost are used in this research to set the priority according to the yearly energy saving rate and initial investment.

Result:

It appears that replacing the existing boiler with high efficiency oil-fired condensing boiler and repairing a building with thicker internal insulation are effective ways to save not only energy usage but also energy cost. It would probably be beneficial for the stakeholder who are related to small-scaled urban regeneration projects such as owners, administrators, specialists, urban regeneration support centers to consider both passive and active systems simultaneously within limited budget.


Keywords: Detached House Standard Model, Energy Conservation Measures, Importance Analysis
키워드: 단독주택 표준모델, 주택정비기술, 중요도 분석

1. 서론
1.1. 연구의 배경 및 목적

기존 도시정비사업은 거주자들의 경제적 측면은 고려하지 않은 채 사업성이 있는 노후단지를 선택하여 전면 철거하고 재건축, 재개발하는 경향이 있었다. 이는 주변지역의 노후화를 가속시키고 젠트리피케이션, 지역 커뮤니티 해체 등의 다양한 사회적 문제를 일으켰다[1]. 이를 개선하기 위해 중앙 정부에서는 2017년 5월 노후 및 쇠퇴한 주거지의 소규모 주택정비에 초점을 맞춘 우리동네살리기, 주거지지원형 등의 도시재생뉴딜사업을 발표하였다. 이 사업은 매년 10조원씩 5년간 총 500곳에 서 진행되는 대규모의 사업인 만큼 사전계획수립과 효율적인 집수리 비용의 집행이 중요할 것으로 사료된다. 본 연구는 소규모 주택정비를 통한 주거환경개선시 필요한 친환경 주택정비기술의 중요도를 분석하여, 한정된 집수리 비용을 효율적으로 사용할 수 있도록 주택정비기술의 우선순위를 도출하는 것이 목적이다.

1.2. 연구의 범위

본 연구에서는 주택정비기술 적용에 따른 건물에너지 성능 및 비용 절감 효과를 분석하기 위해 단독주택 표준모델을 선정하였다. 동적 건물에너지 시뮬레이션 프로그램을 이용하여 에너지소비량 및 투자회수 기간 등의 지표를 이용하여 정량적인 개선치를 도출하였다. 건물성능 향상을 위해 채택한 주택정비기술들의 열전도율 및 열관류율의 단열 성능, 설비의 효율 등의 정보는 에너지절약형 친환경주택의 건설기준(2017.12.15. 시행), 건축물의 에너지절약 설계기준(2017.06.20. 시행), 건축물 에너지효율등급 인증 기준(2017.01.20. 시행)을 참고하여 해당 기준에 적합한 제품 및 재료를 선정하여 분석하였다.


2. 이론적 고찰
2.1. 기존 문헌 고찰

김민경 외(2010)의 연구에서는 전문가를 대상으로 하는 ‘델파이 설문조사’ 방식을 통해 에너지성능 개선을 위한 기술 요소의 우선순위를 도출하고, 시뮬레이션을 통한 각 기술들의 정량적 개선 효과를 분석하였다. 기존 단독주택의 에너지성능 개선효과 우선순위는 벽체 단열강화 > 창문 효율개선 > 창틀 단열 강화 > 기밀성 개선 순으로 연구결과를 보고하였다 [2]. 이성진 외(2017)는 시뮬레이션을 통해 벽체의 단열성능 개선 > 기밀성 향상 > 창호의 열관류율 및 SHGC 개선> 창면적비 증가 순으로 에너지 절감 효과가 나타났다고 보고하였다[3]. 이명주 외(2012)는 단독주택 난방에너지절약을 위한 요소별 에너지 절감률을 창호(37.92%) > 폐열회수기(27.82%) > 외피단열(25.23%) > 기밀성(5.49%) > 단열방식(4.42%) > 벽체열저장능률(3.99%) > 남측창면적비(0.29%) 순의 연구결과를 도출하였다 [4]. 김원석 외(2015)는 장애인 주택의 주거환경 개선을 위해 평균공사비용 대비 에너지절감율을 분석하여 창 교체와 바닥 단열재 보강 기술의 효과가 벽체 단열재보강 보다 우수하다는 연구결과를 보고하였다[5]. 고종철 외(2011) 논문에서는 에너지 절감율과 단가의 상관관계를 바탕으로 한 기여율을 통해 공동주택 최적설계지침 가이드라인을 연구하였다 [6]. 기존 문헌 고찰 결과, 창호 및 벽체 등의 건축적· 패시브적 기술들의 변수를 통한 단독주택 난방에너지성능 개선에 초점을 맞추고 있는 것으로 나타났다. 본 연구에서는 창호 · 벽체와 같은 건축적 변수 외에 절수형 양변기 · LED조명 · 가스 및 기름보일러 등의 설비적 변수를 고려하여 주택정비기술들의 중요도를 분석하고자 한다.

2.2. 도시재생뉴딜사업

2017년 5월 이전까지의 도시재생사업 유형별 사업구조의 경우, 도시재생 활성화 및 지원에 관한 특별법 및 국가균형발전 특별법을 토대로 도시활력 증진지역 개발 사업을 진행해 왔다. 도시활력 증진지역 개발 사업에는 도시경제 기반형, 근린재생형, 도시생활환경개선, 지역역량강화에 대한 내용으로 구성되었다 [7]. 이러한 사업은 단독주택들이 밀집해 있는 소규모 주거지정비사업의 활성화를 일으키지 못하는 경향을 보여 2018년 도시재생뉴딜사업 유형에서는 도시재생사업과 도시활력 증진지역 개발 사업으로 분류하였다. 도시재생사업에는 경제기반형, 중심시가지형, 일반근린형, 주거지지원형 사업유형이 속하며, 도시활력 증진지역 개발사업에는 우리동네 살리기 사업유형이 포함되었다. 주거지재생을 목표를 둔 우리동네살리기는 소규모 저층 주거밀집지역을 대상으로 노후주거지 정비, 공동이용시설 등을 정비하는 사업을 의미한다. 본 연구는 우리동네살리기 사업에 참여하는 행정가, 도시재생지원센터, 집수리 전문가, 주민, 협동조합 등의 참여주체가 집수리시 필요한 정비기술 선정시 활용가능한 집수리 기술의 중요도 분석 결과를 제공하는 것에 의의를 둔다.

2.3. 단독주택 노후도 분석

노후주거지를 정비하는 내용을 포함한 도시재정비촉진사업의 유형을 살펴보면, 재건축사업, 재개발사업, 가로주택정비사업, 저소득층 에너지, 주거환경개선사업, 주거환경관리사업 등으로 분류할 수 있다. 주거환경개선사업이란 도시 저소득 주민이 집단적으로 거주하는 지역으로서 정비기반시설이 극히 열악하고 노후 · 불량건축물이 과도하게 밀집한 지역의 주거환경을 개선하거나 단독주택 및 다세대 주택이 밀집한 지역에서 정비기반시설과 공동이용시설 확충을 통하여 주거환경을 보전 · 정비· 개량하기 위한 사업을 말한다 [8]. 노후주택은 일반적으로 건축물이 훼손되거나 일부가 멸실, 주거환경이 불량한 곳에 위치하거나 도시미관을 저해하는 건축물을 의미한다. 본 연구에서는 준공 후 30년 이상 된 주택을 노후주택으로 명명하였다. 국토교통부와 LH 한국토지주택공사에 의해 발간되고, 건축행정 시스템 세움터에서 확인 가능한 건축통계집 자료에서 용도별 노후건축물 현황을 확인할 수 있다. 2016년 기준, 30년 이상의 노후건축물 중 주거용 건물의 경우, 80.9%로 나타났으며, 주거용 건축물 458만동 중 노후주택은 205만동(44.8%)으로 나타났다. 또한, 국가정보통계시스템(KOSIS)의 자료를 보면 단독주택의 약 48%가 노후주택으로 나타났으며 아파트의 경우 5.9%에 해당하는 가구만이 노후주택의 범주에 속하는 것으로 나타났다. 이로 인해 노후주택과 저소득층의 상관관계 분석을 위해 국토교통 통계누리에서 제공하는 소득계층별 주택 유형을 확인하였고, 2017년 기준, 저소득층의 경우 51.8%에 가구가 단독주택에 거주하는 것으로 나타났다. 위의 데이터 분석을 통해 소규모 집수리 정비 사업시, 거주자의 소득 특성을 반영하여 초기투자비용이 적고 건물의 성능 개선 효과가 우수한 정비기술의 도입이 필요할 것으로 사료된다.

Table 1. 
Investigation of house by types and deterioration, 2016 [Unit: the number of a house]
Classification Nationwide
Detached House Apartment Housing Town House Multiplex Housing
Less than a year 64,254 229,335 14,029 110,702
Less than 1 to 2 years 61,783 309,668 11,461 95,977
Less than 2 to 3 years 56,428 303,895 9,547 82,733
Less than 3 to 4 years 51,403 235,781 11,834 93,083
Less than 4 to 5 years 54,244 217,163 11,043 103,046
Less than 5 to 10 years 232,370 1,490,940 23,447 188,073
Less than 10 to 15 years 259,463 1,779,955 32,527 398,724
Less than 15 to 20 years 321,405 1,836,178 59,153 236,859
Less than 20 to 30 years 958,389 3,035,335 158,646 598,633
Less than 30 to 40 years 722,219 550,465 154,370 85,324
Less than 40 to 50 years 481,300 38,753 6,073 7,407
More than 50 years 704,518 2,176 339 222
Sum 3,967,776 10,029,644 492,469 2,000,783
Deteriorated Housing Ratio (%) 48.09 5.90 32.65 4.65

Table 2. 
Housing Condition Survey by income bracket [Unit: %]
Classification Nationwide
Total Low-income Middle-income High-income
Detached 34.3 51.8 26.0 15.0
Apartment 48.6 28.1 56.8 74.5
Townhouse 2.2 2.2 2.5 1.8
Multiplex 9.2 9.3 10.7 6.2
House in Non-residential 1.6 2.1 1.4 1.2
Living in structures other than dwellings 4.0 6.5 2.7 1.4
Sum 100 100 100 100

2.4. 집수리 예산 지원 정책

집수리시 지원되는 지원제도 중 대표적인 2가지 제도를 고찰하고 요약한 내용은 다음과 같다. 첫째, 산업통상자원부에서 지원하는 ‘저소득층 에너지효율 개선 사업’은 임대주택을 거주하는 국민기초생활 수급자 및 차상위계층 등을 대상으로 창호, 단열, 보일러 등을 가구당 150~300만원 한도로 무상으로 지원해 준다. 둘째, 서울시에서 지원하는 ‘리모델링지원형 장기안심주택제도’는 15년이 지난 전용면적 60㎡ 이하 주택 소유자로 전세 보증금이 2억2000만원 이하까지 신청할 수 있다. 단열공사, 보일러 · 상하수도 배관 교체 등의 리모델링 공사비용은 각 가구를 기준으로 보조하며 지원금은 500만~1000만원이다.

집수리 계획 시 위의 내용을 바탕으로 대상주택이 지원 받을 수 있는 제도를 먼저 파악하여 예산을 책정 후 적용 가능한 주택정비기술을 선정이 필요할 것으로 판단된다. 이러한 기술 선정 과정을 위해 본 연구에서는 저소득층 에너지효율 개선사업 및 기타 지자체의 지원 규모를 참고하였고, 한정된 지원 금액 안에서의 최대한의 효율을 낼 수 있는 주택정비기술의 중요도를 분석함에 의의를 둔다.


3. 연구방법 및 절차 (분석대상선정 및 분석방법)
3.1. 분석 개요

주거환경개선시 한정된 비용으로 최대한의 에너지효율을 낼 수 있는 주택정비기술의 중요도를 분석하기 위하여 동적에너지시뮬레이션을 활용하였다. 단독주택 표준모델을 선정하고 시뮬레이션을 해석을 통해 baseline의 연간 에너지소비량을 구축하였다. 중요도 분석을 통한 기술 적용의 우선순위를 선정하기 위하여 초기투자비용 대비 연간 에너지비용 절감 성능 및 에너지비용 절감 효과가 우수한 주택정비기술을 도출하였다. 분석을 위해 적용되는 기술은 3가지 패시브 기술과 5가지 액티브기술로 분류하였다.

3.2. 시뮬레이션 해석 대상 및 입력데이터

주택정비기술들의 중요도 파악을 위해 단독주택 표준모델을 선정하여 집수리 전· 후의 건물에너지 성능을 비교 분석하였다. 분석을 위해 선정한 단독주택 표준모델은 김정화(2015)가 제시한 저소득층 단독주택으로써 Table 3.과 Fig. 1.에 표준모델에 대한 건축정보 및 평면 이미지를 나타내었다 [9]. 이 표준모델은 2013년 실시된 저소득층 에너지효율 개선사업의 시공지원을 받은 3,061가구 중 단독주택에 해당하는 2,571가구에 대한 현장실사 자료를 바탕으로 도출되었다. 단독주택 표준모델의 창호 단열성능은 저소득층 단독주택의 표본조사를 통해 얻은 열관류율의 평균값으로 설정하였다. 건물 외피중 벽체, 바닥, 지붕의 열관류율은 준공년도를 기준으로 가장 취약한 1980년대의 단열기준을 적용하였다. 환기량의 경우, 사용연수 18~22년 사이 세대의 평균값 1회/Hour로 설정하였다. 조명밀도의 경우, 김원석 외(2015)의 연구에서 제시한 15W/㎡의 값을 적용하였다. Fig. 1.과 Fig. 2.에는 에너지 분석을 위해 사용된 평면도와 열원설비 모델링 구성도를 각각 나타내었다.

Table 3. 
Input Data of Detached House Standard Model (Baseline)
Classification Input Data Note
(Performance Benchmark)
Floor Area (㎡) 44.5 Sample Survey
Ceiling Height (m) 2.3 Sample Survey
Orientation South -
Thermal
Transmittance
(W/㎡·K)
Roof 1.05 The 1980
Wall 1.05 The 1980
Floor 1.05 The 1980
Window 4.46 Sample Survey
Door 2.29 Sample Survey
Location/Weather File Incheon IWEC
Heating Setpoint (℃) 20 Standard
Air Change Rate (ACH) 1 Sample Survey
Internal Gain
(W/㎡)
People 1.49 Default
Equipment 3.21 Default
Heating System (Oil-Fired) Efficiency:85% Sample Survey
Lighting Density (W/㎡) 15 Sample Survey
Operation Schedule (Hour) 24 -
Window-Wall Ratio East 10.8 Sample Survey
West 2.5 Sample Survey
South 24.8 Sample Survey
North 18.6 Sample Survey
Simulation Program DesignBuilder -


Fig. 1. 
Energy Modeling of Detached House Standard Model


Fig. 2. 
Modeling of Underfloor heating and Domestic Hot Water

Table 3.에는 단독주택 표준모델의 에너지해석을 위해 필요한 건축, 기계, 전기설비 등에 대한 설정 값을 정리하여 나타내었다.

3.3. 주택성능개선을 위한 주택정비기술 선정

주택정비기술은 크게 보일러 및 외피 단열성능 개선 등과 같은 에너지성능 개선기술과 방수 · 타일 · 수장 · 가구 공사 등과 같은 안전 · 환경 개선기술로 분류 할 수 있다. 본 연구에서는 에너지성능개선기술에 초점을 맞추어 주택법 시행규칙 제26조 별표 1 장기수선계획의 수립기준 및 기존 논문 등을 참고하여 시뮬레이션 해석이 가능한 주택정비기술을 선별하였다. 선정된 기술들의 성능은 2017 건축물의 에너지절약 설계기준 및 2017 에너지절약형 친환경주택의 건설기준과 같은 국내 · 외 친환경건축물 보급을 위한 설계가이드라인 및 인증기준을 바탕으로 도출하였다. 연구결과의 실용성 향상을 위해 신재생에너지설비와 같은 경제적 부담이 큰 기술은 제외하였다. 또한 주택 개· 보수 시 무분별한 다량의 기술들을 제시하여 혼란, 선정의 어려움 등의 역효과를 최소화 하였다. 본 연구에서는 열원설비 등의 보편적으로 적용이 가능하고 에너지성능과 밀접한 관련이 있는 기술 위주로 주택정비기술을 선정을 하였다. Table 4.에 선정된 기술의 우선순위 분석을 위해 선정한 주택정비기술을 나열하였다.

Table 4. 
Energy Conservation Measures for Energy Performance Improvement
ECMs Energy Conservation Measures Sort Note
1 High Insulated Steel Door Passive Architectural
2 Double-Glazed Window Passive
3 Internal Insulation Reinforcement Passive
4 LED Lighting Active Electrical
5 Condensing Gas-Fired Boiler Active Mechanical
6 Stainless Oil-Fired Boiler Active
7 Condensing Oil-Fired Boiler Active
8 Water-Saving Toilet Bowl Active

3.4. 비용효율 분석 방법
(1) 에너지소비량 및 에너지요금

동적 에너지 시뮬레이션을 통해 산출된 연간 에너지소비량은 난방, 급탕, 조명 등의 항목으로 분류되며, 에너지원으로는 전력, 유류, 가스로 구분된다. 사용된 에너지원의 비용 산출을 위해 월별 에너지 소비량의 데이터를 출력하였다. 조명, 발열기기 등으로 인한 전력 에너지요금은 아래의 (식1)에 의해 산출하였다. 주택정비기술 대안 중 고효율 콘덴싱 가스보일러를 제외한 나머지 주택정비기술들의 난방 열원설비는 기름보일러를 적용하였으며, 한국석유공사 오피넷에서 제공하는 단가를 이용하여 (식2)를 통해 등유에너지 요금을 산정하였다. 프로판가스를 연료로 사용하는 고효율 콘덴싱 가스보일러의 경우, 대한 LPG협회에서 제공하는 가격정보를 이용하였다. 등유보일러에서 고효율 가스보일러로 변경하는 경우, 도시가스 배관 및 밸브 등과 관련된 부속설비의 시공이 불가한 경우가 발생할 수 있어 개별 LPG 가스통을 사용하는 보일러시스템으로 선정하였으며 (식3)을 통해 에너지요금을 도출하였다.

Electric Energy Rates [KRW/year]                                                                                              = {Basic Rate + Energy Rate} + {Basic Rate + Energy Rate × 3.7% (Powerindustry period fund part)} + {Basic Rate + Energy Rate × 10% (VAT portion)}(식1) 
Table 5. 
Electric Rates (KEPCO Residential Low Power 2016.12.01. After Revision)
Basic Rate [KRW/Household] Energy Rate [KRW/kWh]
Below 200 kWh   910 Below 200kWh   93.3
201 ~ 400 kWh 1,600 Above 200kWh 187.9
Exceed 400 kWh 7,300 Exceed 400kWh 280.6

Price of Lamp Oil [KRW/year] = (Lamp Oil Consumption[l/year] × Unit Price[KRW/l])(식2) 
Table 6. 
Price of Lamp Oil (Oil Price Information Service, Opinet, Korea National Oil Corporation 2018.07)
Classification Unit Price [KRW/ℓ]
Lamp Oil 942.2

Price of LPG (KRW/year) = (LPG Consumption[kg/year] × Unit Price[KRW/kg])(식3) 
Table 7. 
Price of LPG(Residential) (Korea LPG Association, http://www.klpg.or.kr/front/pds/price_info.asp?price_year=2018)
Classification Unit Price [KRW/kg]
LPG 1,945

(2) 선정된 주택정비기술의 특성 및 초기투자비용

건물 개 · 보수 시 투자금액이 많을수록 건물 성능 개선 효과는 비례할 것으로 판단된다. 하지만 저소득층의 경우, 낮은 소득 수준과 한정된 지원비용으로 인해 저비용 · 고효율 · 친환경 주택정비기술의 도입이 우선시되어야 한다. 일반적으로 공사비용의 경우, 재료비와 노무비로 구성되는 직접비, 간접비, 이윤으로 분류된다. 본 연구에서의 재료비는 업체 견적 및 건축공사 표준품셈과 신재생에너지설비의 지원 등에 관한 기준 제11조 원별 기준단가를 참고하였다. 노무비는 표준품셈 일위대가와 기존문헌을 참고하여 산정하였다. 간접비는 직접비에 대한 10% 비율, 이윤은 직접비+간접비에 대한 고정 비율로 산정하였다. 또한 부산광역시 서구 집수리사업을 진행하고 있는 징검다리협동조합에서 제공한 견적서 자료를 참고하였다. 현관에 설치된 출입문의 경우, 열관류율 1.23W/㎡·K의 성능을 가진 스틸도어로 적용 후의 성능 분석을 하였다. 창호 개선 부분은 거실, 안방, 침실에 위치한 총 3세트의 창문을 대상으로 열관류율 1.58 W/㎡·K 성능을 가진 로이복층유리 구조의 단창을 적용하였다. 보일러의 경우, 기존 기름보일러(효율 85%)에서 에너지소비효율 1등급 제품인 고효율 콘덴싱 가스보일러로 교체할 경우(ECMs 5)와 효율이 향상된 스테인레스 기름 보일러로 교체한 경우(ECMs 6), 고효율 콘덴싱 기름보일러 (ECMs 7)를 각각 적용하여 비용효율지표에 따른 주택정비기술의 중요도를 분석하였다. 기존 기름보일러에서 동일 에너지원을 사용하는 스테인레스 기름 보일러로 교체 할 경우, 효율 향상, 기름탱크 및 배관 등의 부속품 교체 비용의 절감이 가능할 것으로 사료된다. 가스보일러 교체시 초기투자비용은 연통조립· 배관부속품교체·보온재 · 배관청소 · 철거 비용을 포함하여 산정하였다. Table 8.에 본 연구에서 분석한 주택정비기술들의 성능 · 초기투자비용 등에 대한 정보를 나타내었다.

Table 8. 
Initial Investment and Information of Energy Conservation Measures (100 KRW in Cutting)
EC
Ms
Items Properties
(Performance Benchmark)
Unit
Price
Quantity Total
[KRW]
Detailed Initial Investment
Direct Cost Overhead Margin
1 High Insulated Steel Door U-vale: 1.23 W/㎡·K
(Energy Saving Design Standards of Buildings, 2017)
324,000
[KRW/EA]
1 EA 324,000 268,000 26,800 29480
2 Double-Glazed Window 5CL+12Air+ 5LE w/PVC Framed
U-vale: 1.58 W/㎡·K
(Energy Saving Design Standards of Buildings, 2017)
165,000
[KRW/㎡]
9 ㎡ 1,485,000 1,228,000 122,800 135,080
3 Internal Insulation Reinforcement EPS TYPE 2-2 100mm
Thermal Conductivity: 0.032 W/m·K
(Energy Saving Design Standards of Buildings, 2017)
16,000
[KRW/㎡]
78 ㎡ 1,248,000 1,032,000 103,200 113,520
4 LED Lighting Density : 10 W/㎡ [Power Consumption: 18W]
(The construction of energy-saving, environmentally friendly housing standards, 2017)
26,500
[KRW/EA]
8 EA 212,000 184,000 9,200 19,320
5 Condensing Gas-fired Boiler Efficiency : 92.4% [Capacity: 18,000 Kcal/hour]
(Energy Saving Design Standards of Buildings, 2017)
570,000
[KRW/EA]
1 EA 570,000 471,000 47,100 52,000
6 Stainless Oil-fired Boiler Efficiency : 90% [Capacity: 17,000 Kcal/hour]
(Energy Saving Design Standards of Buildings, 2017)
540,000
[KRW/EA]
1 EA 540,000 450,000 45,000 49,500
7 Condensing Oil-fired Boiler Efficiency : 98% [Capacity: 16,400 Kcal/hour]
(Energy Saving Design Standards of Buildings, 2017)
942,000
[KRW/EA]
1 EA 940,000 777,000 77,700 85,470
8 Water-Saving Toilet Bowl 6 ℓ / flush
(Water Supply and Waterworks Installation Act, 2017)
370,000
[KRW/EA]
1 EA 370,000 306,000 30,600 33,660

(3) 비용효율지표

적용된 기술의 실용성 및 경제성을 파악할 수 있는 지표로 에너지소비량 절감율, 연간 에너지절감비용, 투자비회수기간 등의 지표를 사용하였다. 연간 에너지절감비용의 경우, 단독주택 표준모델(Baseline) 대비 절감된 에너지소비량의 비율로 표시하였다. 투자비회수기간이란 주거환경개선을 위해 적용되는 각 주택정비기술의 초기투자비용을 연간 절감되는 에너지비용으로 나눈 것을 의미한다. 각 기술의 비용적인 효율성을 간편하게 확인할 수 있는 장점이 있지만 화폐의 시간적 가치를 반영하지 않는다는 단점이 있다. 투자비회수기간 지표 외에 생애비용지표를 통해 각 기술의 중요성을 분석하였다. 생애비용지표는 초기투자비용과 건물 생애기간 동안의 운영비용의 시점을 일치시켜 산출한 지표다. 본 연구에서는 각 주택정비기술의 초기투자비용을 시공비용, 생애기간 동안의 운영비용을 건물 운영에 소요되는 에너지요금으로 정의하였다. 시공비용의 지불시점을 생애기간의 매년 말로 가정, 표준모델 및 주택정비기술 대안별 생애비용을 (식6)을 통해 도출하였다 [11]. (식6)에서 물가상승률(i)의 경우 2001년부터 2010년까지 10년간 소비자 물가지수의 평균값인 3.19%를 적용하였으며[12], 은행이자율(R)의 경우 2001년부터 2010년까지 10년간 한국은행의 대출금리 평균값인 6.30%를 적용하였다 [13]. 단독주택의 생애기간의 경우, 건물의 내용연수인 40년을 기준으로 산출하였다 [14]. 단독주택 표준모델의 에너지사용량 대비 주택정비기술들의 에너지개선 효율성을 시공비용과 에너지 절감 비용의 상관관계를 파악할 수 있는 지표를 통해 각 주택정비기술의 중요도를 분석할 수 있을 것으로 사료된다.

Energy consumption reduction %                                                                                         = {(Baseline Energy consumption [kWh/year]  Alternative Energy                     Consumption [kWh/year]) ÷ Baseline Energy consumption [kWh/year]} × 100(식4) 
Simple Payback Period year                                                                           = Initial investment of each Energy Conservation Measures [KRW] Cycle Cost Reduction KRW                                                                              ÷ Life(식5.1) 
Detailed Payback Period year                                                                                         = Initial investment of each Energy Conservation Measures [KRW] ÷ LifeCycle Cost Reduction KRW                                                                                              (식5.2) 
Life Cycle Cost KRW                                                                                                   = Initial investment of each Energy Conservation Measures [KRW] +1+i1+R×1+i1+Rn-11+i1+R-1×Detached House Energy Cost KRW/year(식6) 

4. 연구결과
4.1. 절수형 양변기 도입을 통한 비용 절감

본 절에서는 1회 사용시 물 사용량이 6ℓ이하인 절수형 양변기(로 탱크형 양변기) [15]로 교체할 경우, 기존에 설치된 양변기와의 물 사용량 비교를 통해 비용효율을 분석하였다. 교체되는 양변기의 수량은 1대로 산정하였다. 사용수량에 따른 수도요금 산정을 위해 양변기의 사용횟수 및 사용수량을 결정하는 것이 중요하다. 박진관 외(2011)의 연구에서 현장실측을 통해 산출한 양변기의 일평균 사용횟수는 54회로 나타났으며[16], 환경부 수도정책과에서 제공하는 절수기기설치 회수기간 산정표에는 50회로 나타났다[17]. 본 연구에서는 성인 1명이 하루 5회 사용하는 것으로 가정, 재실 인원 4명이 거주 할 경우의 양변기 일 평균 사용횟수를 20회로 산정하여 분석하였다. 수도요금 산정방식은 서울특별시 아리수 사이버고객센터에서 제공하는 가정용 상하수도 요금계산식을 이용하였다. Table 9.에 절수형 양변기의 성능과 Table 10.에 기본요금 및 수도요금 단가를 명시하였다.

Table 9. 
Specification of water-saving Toilets
Classification Content
Type Low Tank System
Water Usage 6 ℓ/flush
Installation Expenses (Including Labour Costs) 370,000
Number of Uses (Daily) 20
The caliber of water meter 15mm
The number of households 1

Toilets Bowl Water Usage year                                                                                        = Water Usage (l/flush)× Number of Uses (Daily) × 30day × 12 months(식7) 
Water Rates year                                                                                                                     = {Basic Rate + (Annual Water Usage (m3) × Water Utility Bill (Usage Fee)(KRW/m3)) + Sewage Bill + Alloted Charge } × 12 months                                 (식8) 
Table 10. 
Information of Water Rates (Office of Waterworks, Seoul Metropolitan Government, 2018.1.1.)
Classification Water Rate (KRW) Note
Basic Rate 1080 -
Water Utility Bill (Usage Fee) (KRW/㎥) 550 -
Sewage Bill (KRW/㎥) 850 -
Alloted Charge (KRW/㎥) 170 -
Total charges = 1) Water Uility Bill + 2) Sewage Bill + 3) Alloted Charge

일반적으로 가정에서는 양변기뿐만 아니라 세면수전, 씽크수전 등에서 생활용수를 공급받아 물을 사용한다. 양변기의 물 사용량만을 기준으로 기본요금을 산정할 경우, 요금이 적게 산출 될 수 있으므로 사용요금 구분(㎥)을 30초과 50이하 구간을 선정하였다. 기존 양변기의 물 사용량의 경우, 환경부 수도정책과에서 제공하는 절수기기설치 회수기간 산정표 및 절수기기 설치 내용을 참고하여 13ℓ/flush, 19ℓ/flush 2가지 경우로 분류하였다. 절수형 양변기 도입에 따른 수도요금 절감에 대한 결과를 Table 11. 에 나타내었다.

Table 11. 
Economic Analysis of Water-saving Toilets Bowl
Classification Baseline 1 Baseline 2 Water
Water Usage (ℓ/Flush) 13 19 6
Daily Usage (Frequency) 20 20 20
Usage
(㎥)
Daily 0.260 0.380 0.120
Monthly 7.3 11.4 3.6
Yearly 93.6 136.8 43
Water
Bill
(KRW/year)
Basic 12,960 12,960 12,960
Water Utility 51,480 75,240 23,760
Sewage 79,560 116,280 36,720
Alloted Charge 15,912 23,256 7,344
Total Water Bill
(KRW/year)
159,912 227,736 80,784
Proposed Water Usage Saving Ratio (%) Compared to Baseline 1 54
Compared to Baseline 2 69
Proposed Yearly Reduced Cost (KRW) Compared to Baseline 1 79,128
Compared to Baseline 2 146,952
Payback Period (year) Compared to Baseline 1 4.7
Compared to Baseline 2 2.5

분석결과를 살펴보면, 단독주택 표준모델의 기존 양변기의 사용수량을 1회 사용 시 13ℓ로 산정하여 연간 수도요금을 계산한 경우, 159,912원으로 나타났다. 19ℓ로 산정한 경우는 227,736원으로 나타났다. 1회 사용 시 물 사용량이 6ℓ가 소모되는 절수형 양변기의 경우, 연간 수도요금이 80,784원으로 나타났으며, 13ℓ를 사용하는 경우보다 79,128원이 절감되는 것으로 나타났다. 절수형 양변기를 적용한 경우의 투자비회수기간의 경우, Baseline 1과 비교한 경우 4.7년, Baseline 2와 비교한 경우는 2.5년으로 나타났다. Baseline 2 대비 절수형 양변기 시공시 투자비회수 기간이 2.5년으로 나타나 경제성이 우수한 것으로 나타났다. 주택법 시행규칙 장기수선계획의 수립에서는 양변기의 교체시기를 20년 마다 100% 전면 수선할 것을 규칙으로 삼고 있다. 노후 · 쇠퇴한 단독주택에서 위생 및 안전상의 문제로 양변기를 교체 할 때, 1회 사용 수량이 6ℓ 이하인 절수형 양변기로 교체하면 수도요금 절감 효과를 뚜렷하게 확인할 수 있으며, 이는 투자비회수기간이 3년 미만으로 나타나 경제성이 뛰어난 것으로 판단된다. 또한 기존 거주인원 및 일 사용수량이 많을수록 개선 후 투자비회수기간은 더욱 단축 될 수 있을 것으로 사료된다.

4.2. 단독주택 표준모델 에너지소비량

기존 단독주택에서의 주택정비기술을 적용하기 전, 단독주택 표준모델의 에너지사용량과 사용 금액을 Table 12.에 나타내었다.

Table 12. 
Energy Performance Results of Detached House Standard Model (Baseline)
Classification Monthly Energy Performance Results
Usage (kWh) Energy Rate (KRW)
Electricity Fuel Electricity Fuel
JAN. 204 3,674 23,880 364,374
FEB. 184 2,994 16,000 296,918
MAR. 202 2,406 23,450 238,657
APR. 191 1,333 16,740 132,213
MAY. 193 591 16,950 58,626
JUN. 185 46 16,100 4,562
JUL. 189 16 16,520 1,566
AUG. 190 32 16,640 3,132
SEP. 184 107 16,000 10,572
OCT. 195 783 17,160 77,629
NOV. 194 1,912 17,060 189,678
DEC. 204 3,197 23,880 317,123
Sum 2,314 17,091 220,380 1,695,051
Normalize by floor area 52.6 388.43 5,009 38,524

에너지사용량의 경우, 설정온도 유지 및 급탕 에너지 사용을 위해 보일러에 투입된 연료 사용량의 경우 388.4kWh/㎡·year, 조명, 실내 기기에 사용된 전력량은 52.6kWh/㎡·year로 나타났다. 난방에너지 성능과 관련하여 월별 유류 사용량은 1월이 가장 높게 나타났다. 이는 일반적인 우리나라 겨울철 외기온도 및 일사량, 습도 등에 기인한 것으로 판단된다. 연간 전기요금은 220,380원으로 나타났으며, 난방 에너지와 급탕에너지 용도로 사용되는 유류로 인한 연간 에너지 비용은 1,695,051원으로 나타났다. 실제 에너지 빈곤층, 저소득층의 경우에는 난방비 절감을 위하여 시뮬레이션에서 설정한 난방설정온도 20℃보다 낮은 온도 설정 및 난방설비 가동시간 단축 등과 같은 운영을 하고 있을 것으로 사료된다. 따라서 실제 난방에너지 비용은 본 연구에서 나타난 비용보다 낮을 것으로 판단된다.

4.3. 주택정비기술 적용에 따른 에너지 성능 분석

단독주택 표준모델에 선정된 주택정비기술을 적용 한 후 에너지성능 결과를 Table 13.에 나타내었다. 이 표에는 물 사용량에 따른 수도요금을 제외한 에너지 사용량 및 절감율을 표시하였다. 마이너스 절감율 값은 기존 단독주택 대비 에너지소비량이 증가됨을 나타낸 것이다. 에너지 절감률이 가장 크게 나타난 주택정비기술은 내단열 보강으로, 열전도율 0.032 W/㎡ 단열재 두께 100mm를 보강하여 기존 단독주택 표준모델의 벽체의 단열성능을 향상시킨 결과로 사료된다. 열관류율 1.23W/㎡·K에 해당하는 스틸도어의 경우, 단독주택 표준모델의 기본 성능 대비 에너지소비량 절감율이 0.16%로 나타났다. 바닥 및 지붕을 제외한 외벽의 외피면적 대비 출입문 1 개소의 면적비율은 1.87%로 나타나 열손실 개선을 위해 적용되는 고단열 출입문의 성능개선효과는 미비한 것으로 사료된다. 스틸도어의 경우, 단열성능 외에 기밀성능 향상에 따른 침입외기에 의한 부하와 단열성능 향상에 대한 관류부하를 동시에 분석하는 단계가 필요할 것으로 사료된다. 이러한 이유로 시뮬레이션 결과와 실제 에너지성능 결과는 차이가 발생할 수 있을 것으로 사료된다. 적용된 주택정비기술 중 액티브기술에 해당하는 LED조명기기의 경우, 전력사용량에서는 25.53% 절감된 것으로 나타났다. 하지만 내부발열의 감소로 설정온도 유지를 위한 보일러 연료 사용량이 3.49%로 늘어 난 것으로 나타났다. 이는 기존 단독주택의 조명밀도는 15W/㎡ 이지만, 에너지절약형 친환경주택의 건설기준에서 제시하는 10W/㎡를 적용하여 분석한 결과로 사료된다. 단독주택의 경우, 내부발열에 의한 부하 발생 비중이 높은 비주거 건물(Internally dominated)과 다르게 건물 외벽이 외기에 직접 면해 있어 그로 인한 열손실 및 획득이 많은 건축물(Envelope Load Dominated Building) 이다. 내부발열 중 하나인 조명 발열량이 줄어들어 전력 사용량은 줄어들었지만, 겨울철 난방부하의 증가로 에너지 요구량이 증가한 것으로 판단된다. 연도 밖으로 버려지는 40~50℃에 해당하는 잠열 수증기를 재사용하여 우수한 성능을 가진 고효율 콘덴싱 가스보일러를 적용한 결과 난방에너지 절감율은 14%로 나타났다. PVC프레임의 단창으로 구성된 로이복층유리 적용시 에너지 절감율은 4.34%으로 나타났다. 이중창 및 삼중창의 창호를 적용할 경우, 외피에서의 관류부하 저감을 통한 에너지 절감율이 상승할 것으로 판단된다. 그럼에도 불구하고 단창의 창문을 적용한 이유로는 기존 노후 · 쇠퇴한 주택의 외벽 구조체 두께의 부족으로 인한 이중창 및 삼중창 적용의 어려움 및 이들 제품의 높은 초기투자비용을 고려하여 주택정비기술에서 선정을 제외 하였다. 실내등유를 사용하는 열효율 90%와 98%인 기름보일러를 통한 에너지 절감율은 각각 4.89%, 19.16%로 나타났다. 콘덴싱 기름보일러 적용할 경우, 초기투자비용은 일반형(효율 90%) 기름보일러에 비해 약 1.7배 늘어나지만, 약 4배 이상의 에너지절감효과를 볼 수 있는 것으로 나타났다.

Table 13. 
Energy Performance Results of Each ECMs
Items Yearly Energy Usage Results
Energy Usage (kWh) Energy Saving Ratio (%)
Electricity Fuel Sum Electricity Fuel Sum
Baseline 2,315 17,091 19,406 - - -
1 2,314 17,061 19,375 0.04 0.18 0.16
2 2,316 16,248 18,564 0.04 4.93 4.34
3 2,302 12,990 15,292 0.56 24.00 21.20
4 1,724 17,687 19,411 25.53 -3.49 -0.03
5 2,315 14,246 16,560 0.00 16.65 14.66
6 2,315 16,141 18,456 0.00 5.56 4.89
7 2,315 13,374 15,688 0.00 21.75 19.16

4.4. 비용효율지표를 통한 주택정비기술의 중요도 분석

초기투자비용 및 에너지사용량에 따른 연간 에너지 요금 분석 결과를 바탕으로 투자비회수기간 및 생애기간 비용 등의 지표를 이용하여 주택정비기술의 중요도를 파악하였으며, 그 결과를 Table 14.에 나타내었다. 주택정비기술 적용시 절감된 에너지량에 따른 에너지비용의 감소는 단열재를 100mm 보강한 ECMs 3의 경우가 가장 효율적인 주택정비기술로 나타났다. 하지만, 초기투자비용에 따른 연간 에너지비용을 토대로 산출한 투자비회수기간의 경우, 콘덴싱 기름보일러를 적용한 경우가 2.6년으로 나타나 가장 중요도가 높은 주택정비기술로 나타났다. 내단열 보강의 ECMs 3의 투자비회수기간은 3년, 절수형 양변기를 적용한 ECMs 8은 4.7년, 효율이 90% 향상된 기름보일러의 경우 5.7년, LED를 적용한 경우는 10.3년으로 나타났다. 복층유리를 적용한 단창 ECMs 2의 경우, 연간 에너지절감 비용은 3번째로 나타났지만, 가장 높은 초기투자비용으로 인해 투자비회수기간이 12.9년으로 나타났다. LPG(액화석유가스; Liquefied Petroleum Gas)를 연료로 사용하는 고효율 콘덴싱 가스보일러를 적용한 ECMs 5의 분석 결과를 보면, 연료의 발열량 대비 높은 가스 요금으로 인해 투자비의 자본회수 소요를 초과하는 것으로 나타났다. 고효율 콘덴싱 가스보일러 적용시, LPG보다 요금이 저렴한 LNG(액화천연가스; Liquefied Natural Gas) 배관이 설치된 곳에 적용하는 것이 합리적일 것으로 사료된다. 단독주택 표준모델 대비 적용된 주택정비기술들에 대한 비용적인 상관관계 분석을 위해 에너지비용 1% 절감을 위한 추가 소요비용을 분석하였다. 분류된 기술 중에서 Table 14.와 같이 콘덴싱 기름보일러가 적용된 ECMs 7의 경우가 가장 적은 비용으로 에너지절감을 달성할 수 있는 것으로 나타났다. 이는 내단열 보강을 한 ECMs 3에 비해 약 1만원의 비용이 적게 드는 것으로 나타났다. 생애비용 분석을 통해 장기적 관점에서의 비용 절감에 대해 효과적인 주택정비기술은 콘덴싱 기름보일러와 내단열 보강기술로 나타났다. 분석된 자료를 바탕으로 노후· 쇠퇴한 주택의 주거환경 개선시, 한정된 비용으로 최대한의 에너지성능과 관련된 주거환경개선 효과를 극대화하기 위해서는 내부단열 보강과 고효율 열원설비의 교체가 동시에 이루어져야 할 것으로 판단된다.

Table 14. 
Importance Analysis of Energy Conservation Measures for Detached House Standard Model
ECMs Importance Analysis
Energy
& Water
Saving
Ratio
Initial
Expense
Energy Rate by Energy Source
(KRW/year)
Total
Energy
Rate
Energy
Rate
Savings
Energy
Rate
Saving
Ratio
Simple
Pay
back
Period
Detailed
Pay
back
Period
Increasing
Cost per
Energy
Saving
Ratio
Life
Cycle
Costing
% KRW Electricity Fuel Water KRW/year KRW/year % Year Year KRW/% KRW
Baseline - - 220,380 1,695,051 159,912 2,075,343 - - - - - 47,863,788
1 0.16 324,000 220,380 1,692,127 159,912 2,072,419 2,924 0.14 110.8 -1.26 2,314,286 48,120,356
2 4.34 2,310,000 220,710 1,579,150 159,912 1,959,772 115,571 5.57 12.9 1.26 266,607 46,683,376
3 21.20 624,000 213,020 1,288,282 159,912 1,661,214 414,129 19.95 3.0 0.15 62,556 39,560,708
4 -0.03 212,000 140,590 1,754,192 159,912 2,054,694 20,649 0.99 10.3 0.80 212,000 47,599,567
5 14.66 570,000 224,110 3,174,656 159,912 3,558,678 1,483,335 -71.47 -0.2 -0.01 -3,778 82,344,070
6 4.89 540,000 220,380 1,600,881 159,912 1,981,173 94,169 4.54 5.7 0.33 118,843 46,231,951
7 19.16 942,000 220,380 1,326,388 159,912 1,706,680 368,662 17.76 2.6 0.12 53,041 40,303,306
8 54.00 370,000 224,110 1,695,051 80,784 1,999,945 79,128 3.81 4.7 0.25 97,113 46,408,852


5. 결론

본 연구는 중부지방에 남향으로 배치된 단독주택 표준모델을 기준으로 선정된 주택정비기술들의 적용하여 주택 에너지 성능을 분석하였다. 집수리 사업시 필요한 기술의 우선순위 선정을 위해 에너지소비량 및 비용 절감 및 투자회수기간, 생애기간 등의 비용효율 지표를 통해 중요도를 분석하였다. 노후· 쇠퇴한 단독주택 개선시 한정된 비용을 고려, 공사비 대비 최대 에너지성능을 낼 수 있는 주택정비기술의 도출 결과는 아래와 같다.

첫째, 단독주택 표준모델 대비 연간 에너지 사용량에 대한 절감율은 내단열보강-ECMs 3(21.20%), 고효율 콘덴싱 기름보일러-ECMs 7(19.16%), 고효율 콘덴싱 가스보일러-ECMs 5(14.66%)로 나타났다.

둘째, 연간 에너지 요금 절감율에 대한 분석결과, 내단열보강-ECMs 3(19.95%), 고효율 콘덴싱 기름보일러-ECMs 7(17.76%), 로이복층유리-ECMs 2(5.57%)순으로 나타났다.

셋째, 비용효율 지표로 선정한 투자회수기간 및 생애비용의 경우, 고효율 콘덴싱 기름보일러와 내단열 보강 주택정비기술의 효과가 각각 뛰어난 것으로 분석되었다.

넷째, 주택정비기술 중 절수형 양변기 설치를 통한 성능 분석 결과의 경우, 물 사용량 54% 절감, 수도 및 난방· 급탕 등의 전체 요금을 포함한 에너지비용 절감율 3.81%, 생애비용을 기준으로 산출한 투자회수기간은 0.25년으로 나타났다.

향후 건물의 방위별 · 지역별 기후조건 등의 변수를 바탕으로, 외단열 시스템, 야간단열 덧문, 단열벽지, 기밀성 개선, 전열교환기 설치, 태양광 및 태양열 신재생에너지 기술 등 다양한 범위의 주택정비기술 적용에 따른 비용효율 지표 산정 및 분석을 통한 기술 중요도의 도출에 대한 연구가 필요할 것으로 판단된다. 또한, 이번 연구에서 도출된 주택정비기술의 데이터를 바탕으로 현장시공을 통한 개선 전 · 후에 대한 실제 에너지 사용량 조사 및 경제성 분석, 재실자 만족도에 대한 연구의 진행이 수반되어야 할 것으로 사료된다.


Acknowledgments

본 연구는 국토교통부/국토교통과학기술진흥원 도시건축연구사업의 연구비지원(18AUDP-B077107-05)에 의해 수행되었습니다.

This research was supported by a grant (18AUDP-B077107-05) from Architecture & Urban Development Research Program funded by Ministry of Land, Infrastructure and Transport(MOLIT) of Korea government and Korea Agency for Infrastructure Technology Advancement(KAIA).


References
1. 정용식, 도시재생 사업계획과 실무, 건설경제, (2017), p29-30, 재정리.
Yong Sik Jeong, Project plan and practical business, Construction and Economy Daily, (2017), p29-30, edited.
2. 김민경, 김성은, 기존 단독주택의 에너지성능개선을 위한 요소 및 효과에 관한 연구, 서울도시연구, 11(3), (2010), p29-47.
Kim, Min-Kyeong, Kim, Seong-Eun, Technical Factors on Energy Performance Improvement and the Effects for the Existing Detached House, Jounal of SI, 11(3), (2010), p29-47.
3. 이성진, 김종훈, 정학근, 류승환, 이정훈, 저소득층 단독주택의 난방에너지효율 향상 연구, 한국건축친환경설비학회논문집, 11(3), (2017), p212-218.
Lee, Sung-Jin, Kim, Jong-hun, Jeong, Hak-geun, Yoo, Seung-hwan, Lee, Jung-hun, Heating energy efficiency improvement analysis of low-income houses, Journal of KIAEBS, 11(3), (2017), p212-218.
4. 이명주, 김원석, 이우주, 이원택, 건축물에너지절약요소기술 적용에 따른 단독주택 에너지 요구량 절감률 변화에 관한 연구, 대한건축학회논문집, 28(5), (2012), p275-282.
Lee, Myoung-Ju, Kim, Won-Seok, Lee, Woo-Joo, Lee, Won-Taek, A Study about Reduction Rates of Building Energy Demand for a Detached House according to Building Energy Efficient Methods, Journal of AIK, 28(5), (2012), p275-282.
5. 김원석, 이명주, 저소득층 장애인 주택 주거환경 및 에너지 효율 개선을 위한 개·보수 사례 연구, 대한건축학회논문집, 31(1), (2015), p57-64.
Kim, Won-Seok, Lee, Myoung-Ju, The Research on Energy Performance Improvement Renovation Case Studies for the Physically Disabled Low-Income Home Owners, Journal of AIK, 31(1), (2015), p57-64.
6. 고종철, 이종인, 김현배, 신지웅, 고정림, 안병욱, 강승구, 공사비 절감을 위한 공동주택 건축물에너지효율등급 인증 최적설계지침 가이드라인 연구, 한국건축친환경설비학회논문집, (2012), p228-231.
Ko, Jong-Chul, Lee, Jong-In, Kim, Hyun-Bae, Shin, Jee-Woong, Ko, Jung-Lim, An, Byung-Wook, Kang, Seung-Ku, A study on guideline of Building Energy Efficiency Rating certification in Apartment for reducing cost, Journal of KIAEBS, (2012), p228-231.
7. 국토교통부, 도시재생 뉴딜사업 (우리동네살리기) 실행(활성화) 계획 수립 및 사업시행 가이드라인(안), (2018).
Ministry of Land, Infrastructure and Transport, Guidelines for Project Planning and Implementation for the Urban Regeneration New-Deal Project (우리동네살리기), (2018).
8. 국토교통부, 도시 및 주거환경정비법, (2018).
Ministry of Land, Infrastructure and Transport, Built Environment Renewal Development Act, (2018).
9. 김정화, 저소득층 단독주택 난방에너지 기준 및 개선모델 개발 연구, 석사논문, 2015, Feb.
Kim, Jung-Hwa, Heating Energy Baseline and Saving Model Development of Detached Houses for Low-income Households, UST, 2015, Feb.
10. 김성완, 박진경, 김유미, 주거지 도시재생사업을 위한 저비용·친환경 주택기술 중요도 분석, 한국생태환경건축학회 논문집, 17(6), (2017), p207-115.
Kim, Sung-Wan, Park, Esther-Jinkyung, Kim, Yu-mi, Prioritizing Low-cost ‧ Green Technologies for Neighborhood Regeneration, KIEAE Journal, 17(6), p107-115.
11. 송승영, 이수진, 허갑수, 진현호, 제로에너지 공동주택을 위한 주요 설계변수별 비용효율 분석, 대한건축학회논문집, 28(8), (2012), p207-216.
Song, Seung-Yeong, Lee, Soo-Jin, Hur, Kab-Soo, Jin, Hyun-Ho, Cost Efficiency Analysis of Design Elements for a Zero Energy Apartment Building, Jounal of AIK, 28(8), (2012), p207-216.
12. 국가통계포털(KOSIS, www.kosis.kr)) // Korean Statistical Information Servoce (www.kosis.kr)
Korean Statistical Information Servoce (www.kosis.kr).
13. 한국은행경제통계시스템 (https://ecos.bok.or.kr) // Economic Statistics System (https://ecos.bok.or.kr)
Economic Statistics System (https://ecos.bok.or.kr).
14. 지방공기업법 시행규칙, [별표 2] 건축물 등의 내용 연수표 // Enforcement Regulation of the Local Public Enterprise Act, [Schedule 2] Period for duration of architecture and others
Enforcement Regulation of the Local Public Enterprise Act, [Schedule 2] Period for duration of architecture and others.
15. 환경부, 수도법 시행규칙, 별표2 절수설비와 절수기기의 종류 및 기준, (2018).
Ministry of Environment, Enforcement Regulation of the Water Supply and Waterworks Installation Act, [Schedule 2] Types and Standards for Water-Saving facilities and devices, (2018).
16. 박진관, 정홍도, 신용한, 정효민, 정한식, 초절수형 양변기 도입을 위한 경제성 분석에 관한 연구, 대한설비공학회 동계학술발표회 논문집, (2011), p275-278.
Park, Jin-Gwan, Jung, Hong-Do, Shin, Yong-Han, Jeong, Hyo-Min, Jeong, Han-Sik, The Research on Economic Analysis by Introducing Water-saving Toilets, Journal of SAREK, (2011), p275-278.
17. 환경부, 절수제품 사용시 회수기간 산정표, 수도정책과, (2010).
Ministry of Environment, ROI Schedule for using Water-saving devices, Water Supply and Sewerage Policy Division, (2010).